Product Series
|
CASTLE
|
|
Model
|
C1K
|
C2K
|
C3K
|
|
Rated Power
|
VA/W
|
1kVA / 0.7kW
|
2kVA / 1.4kW
|
3kVA / 2.1kW
|
|
Input
|
Nominal
Voltage
|
220VAC
|
|
VoltageRange
|
115 ~ 300VAC
|
|
FrequencyRange
|
46~54Hz(default), user
adjustable within 40~60Hz
|
|
Power
Factor
|
0.97
|
|
Connection
|
IEC320-10A
inlet
|
IEC320-16A
inlet
|
|
Output
|
Voltage
|
220VAC±2%
|
|
Frequency
|
46~54Hz or
50Hz±0.2Hz (Line mode)
50Hz±0.2Hz (Batterymode)
|
|
Waveform
|
Sine Wave
|
|
Distortion
|
3%
|
4%
|
|
Overload
Capability
|
108%~150% for 30 sec.,³150% for 300 ms
|
|
Current
Crest Ratio
|
3:1
|
|
Connections
|
IEC320 * 4
|
IEC320 * 6
|
IEC320 * 3 and
Terminal Block
|
|
Battery
|
Type
|
Sealed, Maintenance free,
Lead-Acid (Panasonic)
|
|
Quantity
|
3 pieces
|
8 pieces
|
|
Back-up
Time (Full load)
|
5 min
|
9 min
|
5 min
|
|
Recharge
Time
|
5 hrs to 90% of capacity after
full load discharge
|
|
Bypass
|
Automatic
Transfer
|
on overload and UPS failure
|
|
Before
UPS Power-on
|
Default “NO”, user adjustable
to “YES”
|
|
VoltageRange
|
80~264VAC (Default), user
adjustable within 80~286VAC
|
|
Transfer Time
|
0 ms; less than 4 ms from
inverter to bypass and vice versa
|
|
LED Indicators
|
Status
|
Load level /Batterylevel,Battery, Utility Power, Inverter, Bypass, Overload,
Fault
|
|
Audible Alarm
|
Bypass, On battery
mode,Batterylow, Overload, Fault
|
|
Acoustic Noise
|
At 1
meter distance
|
45 dBA
|
50 dBA
|
|
Communications
|
DB-9
Port
|
RS-232 Serial Interface
|
|
Intelligent
Slot
|
Options: WebPower, AS400 Card
or WinPower CMC
|
|
Network Surge Protection
|
RJ45 I/O port available for
network or Fax/Modem
|
|
Environmental
|
Operating
Temperature
|
0 ~ 40°C
|
|
Operating
Humidity
|
20 ~ 90% non-condensing
|